Electric Panel Upgrades

HEPElectric Panel Upgrades

Electric Panel Upgrades | Electrical | Mascot

Looking to upgrade your electrical panel in Mascot? At HEP, we know that a modern, efficient electric panel is the heartbeat of your home or business. Our expert team is dedicated to ensuring your power supply is safe, reliable, and capable of meeting the demands of today’s technology. With meticulous attention to detail and adherence to the latest industry standards, we provide upgrades that not only enhance safety but also improve energy efficiency and performance.

Experience peace of mind knowing that our certified professionals use top-quality components and the latest techniques to bring your electrical system up to speed. Whether you’re renovating an older property or upgrading an existing installation, HEP’s electrical panel upgrades offer a smart, long-term investment for your property’s future. Enjoy the confidence of a system built for the challenges of tomorrow, with service excellence starting from your doorstep in Mascot.

What our customers say

Josh butler did an excellent job fixing and explaining my breaker situation. Recommend him for your electrical problems
Fred W. profile photo
Fred W.
Zack came out to give me estimate, He was professional and answered all my questions and helped me get the work finance. Price was pretty fair for the amount of work being done to bring everything to code. There replacing utility pole and outside breaker box
Frank H. profile photo
Frank H.
I called HEP on Monday to request assistance with our breaker panel. Our main breaker went bad and we only had power in half of the house, no a/c. They were booked up for Monday but got to me first thing this morning, Tuesday, and had the main replaced in no time at all. Kudos go to the service man, Jack Loy for the quality of his work. Thank you HEP for the response time and getting us in the cool once again. As it says on the truck, Happy Wife, Happy Life.
Edwin F. profile photo
Edwin F.
Josh Butler came today and reviewed the premise. He acknowledged many issues and was extremely informative about our electrical panel issues. He showed a lot of empathy and concern for our safety, and we appreciate that! He is taking the initiative to make the changes needed to correct the problems with this older property.
Alex B. profile photo
Alex B.
Adam & Josh B, changed my panel out, and done a fantastic job, and had the job done in 3 hours, and had my power back on, I highly recommend them
Susan S. profile photo
Susan S.
Josh butler came and help fix our breaker issue and left us a great estimate to make sure we was safe! Definitely recommend him for your electrical needs
Nichole N. profile photo
Nichole N.
Josh Butler came to my house even after the workday was over an immediately surveyed the situation. Before long he told what the problem was a suggested that I consider putting a whole home surge protector to prevent further issues I am more than pleased to recommend him to anyone who need electrical assistance.
Fizziems V. profile photo
Fizziems V.
Robert was a huge help diagnosing our electrical problem. He waa on time and professional. He also gave so well appreciated advice about surge protectors....thanks Robert and Hep!
Sylvia R. profile photo
Sylvia R.
Electrical panel needed work. Adam F came out and got me squared away, very knowledgeable and professional. Will use HEP going forward.
Chase M. profile photo
Chase M.
Thank you to Jessie and David for working so hard to get my panel in today! They were great guys to spend the day with!
Larra M. profile photo
Larra M.

Why Mascot Properties Need Timely Electric Panel Upgrades

Escalating Electrical Demands

  • Contemporary households and businesses adopt high-current devices: induction stovetops, split-system HVAC, on-site data servers, 22 kW EV chargers
  • Original switchboards from the 1970s-1990s seldom exceed 40 A per phase, leaving negligible spare capacity for modern consumption
  • Building owners in Mascot’s mixed-use zones note frequent breaker trips when multiple appliances run concurrently; a service upgrade eradicates this bottleneck

Compliance Pressures

  • Amendments within the latest AS/NZS 3000 “Wiring Rules” mandate residual current device protection on all final sub-circuits supplying power points and lighting
  • Energy suppliers servicing Mascot require surge protection to be fitted at the point of supply for new and significantly altered installations
  • Insurance underwriters increasingly refuse coverage on dwellings equipped with rewireable fuses; documented panel upgrades maintain policy eligibility

Safety Imperatives

  • Deteriorated bakelite fuse carriers and corroded busbars harbour elevated resistance, generating heat and increasing arc-flash probability
  • Overloaded neutrals accelerate insulation breakdown, posing latent fire risks in densely populated apartment clusters
  • RCD/RCBO retrofits cap touch-voltage exposure to 30 mA, a lifesaving threshold well below ventricular fibrillation currents

Indications Your Switchboard Is Due for Replacement

  • Persistent flickering or dimming lights despite lamp replacement
  • Warm or discoloured panel covers, especially near neutral bars
  • Circuit breakers that refuse to reset or trip without load
  • Audible buzzing inside the board under moderate load
  • Absence of marked RCD test buttons on socket outlets or breakers
  • Aluminium conductors tied to copper busbars without bi-metallic lugs
  • Sub-main insulation brittle to the touch or flaking within the enclosure

HEP’s Structured Upgrade Workflow

Preliminary Load Audit

Licensed engineers log 15-minute interval data across a 7-day period using class-1 power analysers. The resulting diversity profile informs conductor sizing and breaker selection.

Design & Documentation

  • Draft single-line diagrams outlining feeder, metering & distribution architecture
  • Short-circuit and earth-fault calculations to verify component kA ratings
  • Coordination study ensuring downstream breakers clear faults before upstream mains isolate supply

Component Procurement

HEP stocks tier-one switchgear from manufacturers certified to AS/NZS 60898 and IEC 60947-2. Stocking locally avoids construction delays that can plague Mascot refurbishments during peak building seasons.

Installation & Change-Over

A staggered shutdown schedule minimises tenant disruption:

  1. Isolate non-critical circuits first and migrate them to the new board
  2. Maintain essential services (fire pumps, lift motors, security systems) via temporary supply or generator
  3. Execute final cut-over of main tails, energise, and conduct phase-rotation checks

Verification & Handover

  • Insulation resistance testing at 500 V
  • RCD trip-time verification (≤30 mA within 300 ms)
  • Thermal imaging under 80 % load to expose hot spots
  • Issuance of Certificate of Compliance Electrical Work (CCEW) per NSW Fair Trading regulations

Safety and Standards Alignment

AS/NZS 61439 Low-Voltage Switchgear

HEP fabricates assemblies as “Verified Assemblies” rather than “Type Tested” only, allowing tailoring without compromising compliance.

Service and Installation Rules NSW

  • Clearances around the board: minimum 1 m front workspace, 2.1 m headroom
  • IP23 minimum ingress protection for outdoor enclosures exposed to Mascot’s occasional coastal spray
  • Colour coding: red/white barrier tape for live busbars, orange sheathing on consumer mains

Arc Fault Mitigation

  • Current-limiting breakers reduce let-through energy, safeguarding adjacent equipment
  • Arc-flash labels state incident energy (cal/cm²) for PPE selection by maintenance staff
  • Optional arc-flash detection relays trip mains within 2 ms upon sensing plasma light spectrum

Advanced Protection Technologies

Residual Current Devices (RCD) and RCBOs

  • Combination Type A RCBOs detect both AC and pulsating DC fault currents, vital for circuits feeding inverter-driven air-conditioning
  • Periodic auto-reclosing RCBOs reset after verifying fault clearance, reducing downtime for refrigeration lines

Surge Protective Devices (SPD)

Mascot’s summer storm cells and proximity to Sydney Airport’s radar transmissions elevate transient overvoltage exposure. HEP installs:

  • Type 1 spark-gap diverters at main boards to shunt direct lightning energy
  • Type 2 MOV modules downstream for fine clamping
  • Remote visual indicator contacts feeding BMS alarm inputs

Arc Fault Detection Devices (AFDD)

AFDDs monitor high-frequency signatures unique to series & parallel arcing. HEP includes them on:

  • Bedrooms in heritage terraces with timber framing
  • Audio-visual circuits in recording studios to prevent data corruption via arc noise

Integration with Renewable Energy and Electric Mobility

Solar Photovoltaic Compatibility

  • Hybrid inverters demand dual supply isolators: grid and battery. HEP allocates segregated DIN-rail space for grid-interactive breakers
  • Net-metering CT coils are routed through dedicated metering chambers ensuring accuracy

Battery Storage Readiness

  • Panels pre-fitted with 125 A breakers wired to a battery combiner can expedite future installations
  • Ventilation grills carved in switchboard sides maintain lithium-ion cell temperature norms per AS/NZS 5139 guidelines

Electric Vehicle Charger Provisioning

  • Three-phase wallbox chargers needing 32 A per phase have dedicated RCBOs and load-shedding relays communicating over Modbus
  • Demand-management logic stalls charging when household consumption surpasses an adjustable threshold, preventing main breaker nuisance trips

Business Continuity Planning During Upgrades

Staged Implementation for Commercial Premises

  • After-hours cut-overs conducted between 10 pm and 5 am to align with retail downtime
  • Pre-wired interim distribution islands erected to sustain POS and security systems
  • Isolation permits requested from network operator at least 10 working days prior to minimise outage windows

Data Centre and Server Room Considerations

  • Dual UPS input feeds with make-before-break manual transfer switches keep virtual machines live
  • Infrared thermography of termination lugs executed quarterly forms part of an ongoing preventative maintenance agreement

Fire Risk Reduction Strategies

  • Halogen-free, flame-retardant switchboard panels slow fire propagation; tested to UL 94 V-0 rating
  • Cable ladders are fitted with intumescent pillows where they penetrate fire-rated walls between building zones
  • HEP labels circuits clearly so firefighters can de-energise affected areas swiftly in the event of emergency

Sustainable Materials Selection

Recyclable Metals

  • Bare copper busbars sourced from ISO 14001-certified smelters
  • Powder-coated steel enclosures with low-VOC finishes decrease site emissions

Energy-Efficient Auxiliary Equipment

  • LED pilot lights draw <0.6 W each
  • Smart meters transmit via Zigbee mesh, eliminating separate power supplies and reducing parasitic load by 12 kWh yearly per site

Smart Switchboards Enable Real-Time Insights

Embedded Metering

  • Class 0.5 S revenue-grade meters measure bidirectional active and reactive energy for every outgoing circuit
  • Data is logged locally and pushed to cloud dashboards, allowing facility managers to:
    • Track tenants’ consumption for cost recovery
    • Detect unusual load spikes pointing to failing equipment
    • Compare baseline usage pre- and post-retrofit to quantify efficiency gains

Predictive Maintenance

AI algorithms crunch breaker cycle counts and thermal trends to schedule servicing before faults escalate.

Remote Operation

Motorised main switches can be tripped or re-closed from smartphones, beneficial during major weather events when personnel cannot access plant rooms safely.

Upgrading Multi-Tenant and Strata Buildings

Individual Tariff Metering

  • HEP distributes parallel 35 mm² copper busbars feeding modular metering stacks
  • Each tenant receives a lockable isolator per NSW strata regulations

Shared Services Segregation

  • House power circuits (lifts, lighting, car-park exhaust fans) sit behind dedicated meters so costs flow to the owners’ corporation rather than individual lots
  • Power-factor correction staged capacitors improve the building’s aggregate power factor to >0.95 lag, avoiding penalty charges

Future-Proof Cabling Strategies

Allowance for Data and Power Convergence

HEP designs conduit pathways that accommodate both CAT-6A data lines and segregated low-voltage lighting feeds. By planning spare duct capacity and clearly colour-coding conduits, future renovations can deploy power-over-Ethernet luminaires or building-automation sensors without disruptive wall chasing.

Modular Switchboard Architecture

Panels assembled with removable chassis sections, slide-in metering modules, and busbar extension kits make it easy to:

  • Incorporate battery storage inverters as solar penetration rises
  • Expand tenant metering for subdivided commercial floors
  • Integrate power-factor correction banks to curb reactive energy charges

Each modular component adheres to AS/NZS 61439, guaranteeing interoperability and third-party certification.

Detailed Component Selection Guide

Main Switch

  • 4-pole, 63 A–250 A rating depending on calculated demand
  • Positive contact indication windows verify full blade insertion

Circuit Breakers

  • Curve C for general-purpose outlets
  • Curve D for motor loads such as car-park ventilation fans
  • Breaking capacity matched to network prospective fault current, typically 6 kA for inner-urban Mascot feed, 10 kA near substations

Busbars

  • Solid electrolytic-tough-pitch copper, 20 mm × 5 mm cross-section for up to 250 A
  • Silver-plated joints reduce contact resistance, enhancing longevity

Neutral & Earth Bars

  • High-integrity earth link devices simplify periodic earth-continuity testing
  • Clearly segregated MEN link accessible via removable cover for safety

Enclosures

  • IP42 indoor, IP56 outdoor with rainhood
  • Powder-coat colour RAL 7035 (light grey) reflects heat, blending with modern facades

Equipment Testing Protocols

  • Primary injection up to 600 A ensures breaker withstand capacity
  • Secondary injection of RCD circuits confirms trip curves and time/current selectivity
  • Voltage-drop measurements between mains origin and furthest outlet verify compliance with the <5 % rule

Common Installation Challenges and Mitigations

Limited Wall Space in Older Terraces

HEP implements recessed switchboards only 110 mm deep, freeing hallway space while maintaining required clearances.

Asbestos Backing Boards

Certified removalists dispose of legacy asbestos linings prior to new board installation, with air-monitoring reports issued to building owners.

Unbalanced Phase Loading

  • Load logging reveals phases with >20 A imbalance
  • Conductors are reshuffled during upgrade to within 10 % variance, leading to more stable voltage and reduced neutral heating

Business Continuity: Case Study in Retail Precinct

A cluster of boutique cafes and fashion outlets along Bourke Road relied on an ageing fuse board dating back to the early 1980s.

Project Outline

  • Replace 100 A ceramic fuse assembly with 250 A form-4b metal-clad board
  • Install dual 160 A moulded-case circuit breakers feeding two retail wings
  • Integrate cashless metering system enabling each storefront to access live consumption data

Key Outcomes

  • Supply interruptions decreased by 84 % after upgrade
  • Peak demand reduced by 6.7 kW due to improved power factor
  • Energy retailer granted a downstream connection incentive recognising new-generation load-control gear

Environmental Conditions Specific to Mascot

Humidity and Corrosion Control

  • Proximity to Botany Bay introduces salt-laden air that accelerates galvanic corrosion on switchgear
  • HEP counters this through:
    • Epoxy-coated copper busbars
    • Marine-grade stainless-steel hardware (AISI 316)
    • Dehumidifier pods inserted inside sealed enclosures

Acoustic Considerations Near Flight Paths

Mascot’s location under Sydney Airport’s approach path demands sound-proofing of building fabric. HEP selects breakers with low mechanical resonance and mounts boards on neoprene pads, preventing vibration from aircraft noise transferring into walls.

Ongoing Maintenance Recommendations

  • Conduct six-monthly RCD push-button tests to ensure mechanical integrity
  • Schedule infrared scans annually, ideally during summer when air-conditioning load peaks
  • Keep enclosure vents clear of dust buildup that impedes natural convection cooling

Residential vs Commercial Panel Upgrade Nuances in Mascot

Upgrading a switchboard in a single-family terrace differs markedly from reconfiguring a panel in a bustling retail outlet or light-industrial workshop. Recognising these distinctions allows HEP to fine-tune designs for each property type while maintaining consistent adherence to safety and performance standards.

Residential Focus Points

  • Space Constraints: Many Mascot homes have panels embedded in narrow hallways or external meter boxes. HEP selects slimline RCBOs and compact surge-protection devices to maximise available space without sacrificing functionality.
  • Aesthetic Integration: Decorative cover plates, recessed enclosures, and colour-matched faceplates ensure the new board blends with interior finishes.
  • Lifestyle Loads: Growing numbers of home offices, smart refrigeration, and high-wattage induction cooktops require diversified branch circuits. HEP integrates dedicated breakers for media racks, data points, and kitchen appliances.
  • Noise Sensitivity: RCDs with low mechanical chatter and vibration-resistant terminals preserve a peaceful indoor environment.

Commercial and Industrial Considerations

  • Demand Diversity: Restaurants, gyms, and light-manufacturing spaces experience fluctuating loads. HEP implements demand-controlled contactors that shed non-critical equipment during peak draw, safeguarding supply integrity.
  • Equipment Redundancy: Dual main switches and bypass rails enable panel maintenance without shutting down mission-critical machinery or point-of-sale terminals.
  • High Fault Levels: Three-phase panels rated to 25 kA or 36 kA withstand the elevated prospective short-circuit currents typical near substation feeders running beneath Mascot’s commercial corridors.
  • Compliance Documentation: Detailed single-line diagrams and lock-out/tag-out procedures assist facility managers in meeting workplace safety audits.

Future-Proof Cabling Strategies

Allowance for Data and Power Convergence

HEP designs conduit pathways that accommodate both CAT-6A data lines and segregated low-voltage lighting feeds. By planning spare duct capacity and clearly colour-coding conduits, future renovations can deploy power-over-Ethernet luminaires or building-automation sensors without disruptive wall chasing.

Modular Switchboard Architecture

Panels assembled with removable chassis sections, slide-in metering modules, and busbar extension kits make it easy to:

  • Incorporate battery storage inverters as solar penetration rises
  • Expand tenant metering for subdivided commercial floors
  • Integrate power-factor correction banks to curb reactive energy charges

Each modular component adheres to AS/NZS 61439 standards for low-voltage switchgear assemblies, guaranteeing interoperability and third-party certification.

Case Example: Multi-Storey Apartment Retrofit

A recent HEP project involved a twelve-level residential tower built in the 1990s. The original main switchboard provided 250 A per phase but lacked RCD protection and exhibited severe conductor overheating on the neutral bar. HEP’s upgrade roadmap proceeded as follows:

  1. Installed a temporary generator feed to maintain elevator and emergency-lighting operation during change-over
  2. Demolished the legacy switchboard and transplanted metering CTs into a new 400 A busbar chamber with 50 kA fault rating
  3. Deployed 36 RCBO sub-mains to individual floor distribution boards, each labelled to strata standards for rapid fault identification
  4. Added dual Type 2 surge diverters and an advanced power-quality analyser that streams harmonic data to the building manager’s dashboard

Post-commissioning thermal scans showed a 12 °C reduction in conductor surface temperature under full load, validating the efficacy of copper bus re-engineering and balanced phase allocation. Occupants immediately benefitted from steadier lighting, fewer nuisance trips, and headroom for future EV-charger installations in the basement parking levels.

Areas We Serve

AlcoaAllardtAltamontAndersonvilleApisonAthensBean StationBeersheba SpringsBelvidereBentonBirchwoodBlaineBlountvilleBluff CityBricevilleBristolCalhounCaryvilleCharlestonChattanoogaChurch HillClairfieldClevelandClintonCoalmontCollegedaleCookevilleCopperhillCorrytonCosbyCowanCrab OrchardCrossvilleCumberland GapDandridgeDaytonDecaturDecherdDeer LodgeDelanoDucktownDuffDunlapElizabethtonEloraEnglewoodErwinEstill SpringsEtowahEvensvilleFarragutFayettevilleFlintvilleFountain CityFriendsvilleGatlinburgGeorgetownGrandviewGraysvilleGreenbackGreenevilleGruetli-LaagerGuildHallsHarrimanHarrisonHarrogateHeiskellHelenwoodHillsboroHixsonHuntlandHuntsvilleJacksboroJamestownJasperJefferson CityJellicoJohnson CityJonesboroughKarnsKelsoKingsportKingstonKnoxvilleKodakLa FolletteLake CityLancingLenoir CityLookout MountainLoudonLouisvilleLuttrellLynchburgMadisonvilleManchesterMaryvilleMascotMaynardvilleMcDonaldMcMinnvilleMonteagleMontereyMorristownMountain CityMulberryNew MarketNew TazewellNewcombNewportNiotaNorrisOak RidgeOakdaleOcoeeOld FortOliver SpringsOneidaOoltewahPalmerPelhamPetrosPhiladelphiaPigeon ForgePikevillePioneerPowellRelianceRicevilleRobbinsRockfordRockwoodRogersvilleRutledgeSale CreekSequatchieSeviervilleSewaneeSeymourSharps ChapelShelbyvilleSignal MountainSoddy-DaisySouth PittsburgSpartaSpeedwellSpring CityStrawberry PlainsSunbrightSweetwaterTalbottTazewellTellico PlainsTen MileThorn HillTownsendTracy CityTullahomaTurtletownVonoreWallandWartburgWashburnWhite PineWhitwellWinchesterWinfield
HEP
Book Online
(423) 819-7773