When the wind howls across Altamont’s ridges and the grid takes an unexpected dip, HEP keeps the lights on with a fleet of rugged, high-efficiency generators designed for nonstop duty. Engineered to start in seconds and sip fuel responsibly, each unit is backed by smart monitoring tech that alerts our technicians before you ever notice a flicker—so your bakery ovens, server racks, or family movie night stay perfectly powered.
From turnkey installation to round-the-clock maintenance, our local team treats every call like mission control. Whether you need a compact standby unit for a storefront or a multi-megawatt solution for industrial operations, we tailor the system, secure the permits, and test under load until you’re certain it can shoulder the storm. Trust HEP to deliver continuous energy supply that feels seamless, safe, and ready whenever Altamont needs it most.
FAQs
What types of continuous-duty generators do you supply and install in Altamont?
We carry a full line of industrial-grade diesel, natural-gas and bi-fuel generators that are specifically rated for prime or continuous duty. Sizes range from 20 kW mobile units for small construction sites to multi-megawatt stationary packages for data centers, hospitals and manufacturing plants. Enclosures are available in weather-proof, sound-attenuated or walk-in configurations, and all models meet the latest UL, NFPA 110 and EPA emissions standards.
How do I determine the right generator size for my home or business?
Proper sizing starts with a detailed load analysis. Our engineers list every critical device, record both running and in-rush (starting) amperage, account for single-phase and three-phase loads, power factor and future expansion plans. We then apply industry sizing rules (typically 75–80 % average load for diesel, 80–90 % for natural gas) and verify with software simulations. A site visit is included to evaluate space, fuel storage and ventilation requirements before we recommend a specific kW rating.
How fast will the generator restore power when the grid fails?
For most commercial applications we pair the generator with an automatic transfer switch (ATS) that senses a utility failure within 1–2 seconds and signals the generator to start. Diesel sets reach rated speed and voltage in 7–10 seconds; natural-gas units average 10–15 seconds. Load is transferred automatically once stable voltage is confirmed, so total outage time is usually under 15 seconds. If zero interruption is required, we can design a parallel system with UPS batteries to provide seamless ride-through.
Do you offer maintenance and remote monitoring services?
Yes. Continuous-duty generators must be exercised under load and inspected regularly to ensure reliability. We provide customizable service agreements that include monthly visual checks, quarterly preventive maintenance, annual load-bank testing and 24/7 emergency response. Cellular and Ethernet monitoring options transmit real-time data on fuel level, coolant temperature, battery health and alarm status to our service center and to your smartphone, allowing proactive issue resolution.
What permits or regulatory approvals are needed for a generator installation in Altamont?
In Altamont, stationary generator projects typically require (1) a building permit for the concrete pad or enclosure, (2) an electrical permit for wiring and ATS connections, and (3) an air-quality permit from the county’s Air Pollution Control District if the engine exceeds 50 HP. Noise ordinances limit sound levels at the property line, so an acoustic enclosure or barrier may be needed. Our project managers handle all drawings, load calculations, permit applications and inspections on your behalf.
How fuel-efficient and environmentally friendly are your continuous-power solutions?
Our latest Tier 4 Final diesel generators achieve up to 6 % lower fuel consumption than previous models through high-pressure common-rail injection and advanced after-treatment. Natural-gas units produce roughly 20 % lower CO₂ and virtually no diesel particulate matter, making them ideal for extended runtime. We also offer hybrid packages that integrate solar PV, battery storage and smart controls to prioritize renewable energy, automatically cycling the generator only when loads or state-of-charge require it.